CVE-2026-3611

Published: Mar 12, 2026 Last Modified: Mar 12, 2026
ExploitDB:
Other exploit source:
Google Dorks:
CRITICAL 10,0
Attack Vector: network
Attack Complexity: low
Privileges Required: none
User Interaction: none
Confidentiality: N/A
Integrity: N/A
Availability: N/A
CRITICAL 10,0
Attack Vector: network
Attack Complexity: low
Privileges Required: none
User Interaction: none
Scope: changed
Confidentiality: high
Integrity: high
Availability: high

Description

AI Translation Available

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

306

Missing Authentication for Critical Function

Draft
Common Consequences
Security Scopes Affected:
Access Control Other
Potential Impacts:
Gain Privileges Or Assume Identity Varies By Context
Applicable Platforms
Technologies: Cloud Computing, ICS/OT
View CWE Details
https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-0…
https://www.cisa.gov/news-events/ics-advisories/icsa-26-069-03